362 Fieldbus control through the embedded fieldbus interface (EFB)
Modbus function codes
The table below shows the Modbus function codes supported by the embedded
fieldbus interface.
Code
Function name
Description
01h
Read Coils
Reads the 0/1 status of coils (0X references).
02h
Read Discrete Inputs
Reads the 0/1 status of discrete inputs (1X
references).
03h
Read Holding Registers Reads the binary contents of holding registers (4X
references).
05h
Write Single Coil
Forces a single coil (0X reference) to 0 or 1.
06h
Write Single Register
Writes a single holding register (4X reference).
08h
Diagnostics
Provides a series of tests for checking the
communication, or for checking various internal
error conditions.
Supported subcodes:
• 00h Return Query Data: Echo/loopback test.
• 01h Restart Comm Option: Restarts and
initializes the EFB, clears communications event
counters.
• 04h Force Listen Only Mode
• 0Ah Clear Counters and Diagnostic Register
• 0Bh Return Bus Message Count
• 0Ch Return Bus Comm. Error Count
• 0Dh Return Bus Exception Error Count
• 0Eh Return Slave Message Count
• 0Fh Return Slave No Response Count
• 10h Return Slave NAK (negative acknowledge)
Count
• 11h Return Slave Busy Count
• 12h Return Bus Character Overrun Count
• 14h Clear Overrun Counter and Flag
0Bh
Get Comm Event
Counter
Returns a status word and an event count.
0Fh
Write Multiple Coils
Forces a sequence of coils (0X references) to 0 or
1.
10h
Write Multiple Registers Writes the contents of a contiguous block of
holding registers (4X references).
16h
Mask Write Register
Modifies the contents of a 4X register using a
combination of an AND mask, an OR mask, and the
register’s current contents.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...