184 Parameters
Defines the motor load curve together with
parameters
and
Defines the break point frequency of the load
curve ie. the point at which the motor load curve
begins to decrease from the value of parameter
towards the value of
parameter
.
See parameter
.
45.00 Hz
1.00…500.00 Hz Break point for the motor load curve.
10 = 1 Hz
Motor nominal
temperature rise
Defines the temperature rise of the motor above
ambient when the motor is loaded with nominal
current. See the motor manufacturer's
recommendations.
The unit is selected by parameter
80 °C or
176 °F
0…300 °C or
32…572 °F
Temperature rise.
1 = 1°
No.
Name/Value
Description
Def/
FbEq16
Motor nominal
temperature rise
Temperature
Time
Ambient temperature