Fieldbus control through the embedded fieldbus interface (EFB) 351
Control Word
Control Word for the ABB Drives profile
The table below shows the contents of the fieldbus Control Word for the ABB
Drives control profile. The embedded fieldbus interface converts this word to
the form in which it is used in the drive. The upper case boldface text refers to
State transition diagram for the ABB Drives profile
Bit
Name
Value STATE/Description
0
OFF1_
CONTROL
1
Proceed to READY TO OPERATE.
0
Stop along currently active deceleration ramp.
Proceed to
OFF1 ACTIVE
; proceed to
READY TO
SWITCH ON
unless other interlocks (OFF2, OFF3) are
active.
1
OFF2_
CONTROL
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON
INHIBITED
.
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
Warning:
Ensure that the motor and driven machine
can be stopped using this stop mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION D
.
Note:
Run enable signal must be active; see the drive
documentation. If the drive is set to receive the Run
enable signal from the fieldbus, this bit activates the
signal.
0
Inhibit operation. Proceed to
OPERATION INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP FUNCTION
GENERATOR: OUTPUT D
.
0
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
5
RAMP_HOLD
1
ramp function. Proceed to
RAMP FUNCTION
GENERATOR: ACCELERATOR D
.
0
Halt ramping (Ramp Function Generator output held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...