346 Fieldbus control through the embedded fieldbus interface (EFB)
signal is the desired source or destination for that particular drive control
signal. The
Function/Information
column gives a description of the parameter.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
Operating mode Embedded fieldbus
Selects fieldbus as the source for the start
and stop commands.
OTHER SELECTIONS
EFB references can be selected as the source at virtually any signal selector parameter
by selecting
, then either
.
SYSTEM CONTROL INPUTS
(reverts to
)
Saves parameter value changes (including
those made through fieldbus control) to
permanent memory.