Parameters 241
Outlet maximum
pressure warning
level
Defines the level at which drive should generate
the outlet maximum pressure warning.
0.00 bar
0.00...
32767.00 bar
Outlet maximum pressure warning level.
1 = 1 bar
Outlet maximum
pressure fault
level
Defines the level at which drive should generate
the outlet maximum pressure fault.
0.00 bar
0.00...
32767.00 bar
Outlet maximum pressure fault level.
1 = 1 bar
Inlet minimum
pressure
protection
Enables inlet minimum pressure protection
function.
Disabled
Inlet minimum pressure protection is disabled.
0
Warning
Inlet minimum pressure protection function
generates warning
when the pressure is below the level defined with
parameter
Inlet minimum pressure warning
for a time set in
1
Fault
Inlet minimum pressure protection function
generates fault
when the pressure is below the level defined with
parameter
Inlet minimum pressure fault level
for a time set in
.
2
Warning/Fault
Inlet minimum pressure protection function first
generates a warning when the pressure is below
the level defined with parameter
minimum pressure warning level
for a time set in
If the pressure continues to fall below the level
defined with parameter
, a fault is generated.
3
Inlet minimum
pressure warning
level
Defines the level at which drive should generate
the inlet minimum pressure warning.
0.00 bar
0.00...
32767.00 bar
Inlet minimum pressure warning level.
1 = 1 bar
Inlet minimum
pressure fault
level
Defines the level at which drive should generate
the inlet minimum pressure fault.
0.00 bar
0.00...
32767.00 bar
Inlet minimum pressure fault level.
1 = 1 bar
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...