342 Fieldbus control through the embedded fieldbus interface (EFB)
Connecting EIA-485 Modbus RTU terminal to the drive
Connect the fieldbus to the EIA-485 Modbus RTU terminal on the RIIO-01
module which is attached on the control unit of the drive. The connection
diagram is shown below.
...
Process I/O (cyclic)
Service messages
(acyclic)
Data flow
Control Word (CW)
References
Status Word (SW)
Actual values
Parameter R/W
requests/responses
Fieldbus controller
Fieldbus
Driv
Termination OFF
Termination ON
1)
1)
The device at both ends on the fieldbus must have termination set to ON.
ON
1
ON
1
ON
1
B +
A -
DGND
Driv
Termination OFF
ON
1
ON
1
ON
1
B +
A -
DGND
Driv
Termination ON
ON
1
ON
1
ON
1
B +
A -
DGND