Fault tracing 307
A2B3 Earth leakage
Drive has detected load
unbalance typically due
to earth fault in motor or
motor cable.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor
or motor cables by measuring
the insulation resistances of
motor and motor cable. See
chapter
Electrical installation
,
section
Checking the insulation of
the assembly
in the
Hardware
manual
of the drive. If an earth
fault is found, fix or change the
motor cable and/or motor.
If no earth fault can be detected,
contact your local ABB
representative.
A2B4 Short circuit
Short-circuit in motor
cable(s) or motor.
Check motor and motor cable
for cabling errors.
Check motor and motor cable
(including phasing and
delta/star connection).
Check for an earth fault in motor
or motor cables by measuring
the insulation resistances of
motor and motor cable. See
chapter
Electrical installation
,
section
Checking the insulation of
the assembly
in the
Hardware
manual
of the drive.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
01 a short circuit in the
upper IGBT of the
U-phase
02 a short circuit in the
lower IGBT of the
U-phase
04 a short circuit in the
upper IGBT of the
V-phase
08 a short circuit in the
lower IGBT of the
V-phase
10 a short circuit in the
upper IGBT of the
W-phase
20 a short circuit in the
lower IGBT of the
W-phase
40 DC capacitor short
circuit
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...