242 Parameters
Defines the delay time at which the pressure
supervisions are inactive.
You can adjust check delay for a system in which
the pressure does not increase immediately after
starting the motor.
3.00 s
0.00...3600.00 s Pressure check delay time.
1 = 1 s
Defines the dry run current limit. When the actual
current goes below the dry run current limit for a
defined time (
), the drive considers it as a
dry run condition and trips on the fault,
.
Note:
This parameter is not applicable, if the
parameter
selection is set to
DI.
0.00 A
0.00...3000.00 A Current limit.
100 = 1
Defines the time to monitor dry run current limit.
After the defined time elapses, the drive
considers it as dry run condition and trips on the
fault,
Note:
This parameter is not applicable, if the
parameter
is DI.
120.0
1.0...300.0 s
Run trip monitor time.
10 = 1
Defines the rest time to reset the dry run fault
(
). The drive starts automatically if it
receives a start command.
120.0
1.0...18000.0 s
Dry run reset time.
10 = 1
83
Settings for the pump cleaning sequence.
See section
(page
Displays the status of pump cleaning.
Disabled
Pump cleaning is disabled.
0
Clean pump
Pump cleaning is active.
1
No triggers
configured
Pump cleaning is not active.
2
Waiting for
triggering
Waiting for triggering signal.
3
Displays the pump cleaning progress.
0
0.0...100.0%
Percentage
10 = 1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...