Parameters 181
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog
input selected by parameter
and an analog output.
The following settings are required:
• Set the hardware jumper or switch related to
the analog input to
U
(voltage). Any change
must be validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
(volt).
• In parameter group
, set the
source selection parameter of the analog
output to
.
The analog output feeds a constant current
through the sensor. As the resistance of the
sensor increases along with its temperature, the
voltage over the sensor increases. The voltage is
read by the analog input and converted into
degrees.
5
2 × Pt100 analog
I/O
, but with two
sensors connected in series. Using multiple
sensors improves measurement accuracy
significantly.
6
3 × Pt100 analog
I/O
, but with three
sensors connected in series. Using multiple
sensors improves measurement accuracy
significantly.
7
Direct
temperature
The temperature is taken from the source
selected by parameter
. The value of the source is assumed to be
degrees Celsius.
11
Defines the fault limit for temperature
supervision function 2. When measured
temperature 1 exceeds the limit, the drive
trips on fault
The unit is selected by parameter
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring
function 2.
1 = 1 unit
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...