128 Parameters
Selects the forced current vector rotation mode
at low speeds.
When smooth start mode is selected, the rate of
acceleration is limited by the acceleration and
deceleration ramp times. If the process driven by
the permanent magnet synchronous motor has
high inertia, slow ramp times are recommended.
Note
: Can be used for permanent magnet
synchronous motors only.
Disabled
Disabled.
0
Enabled always
Enabled always.
1
Start only
Enabled when starting the motor.
2
Current used in the current vector rotation at low
speeds.
Increase the smooth start current if the
application requires motor shaft swinging to be
minimized.
Note
: Accurate torque control is not possible in
the current vector rotation mode.
Note
: Can be used only for permanent magnet
synchronous motors.
50.0%
10.00...100.0%
Value in percent of the nominal motor current.
1 = 1%
Output frequency up to which the current vector
rotation is used. See parameter
.
Note
: Can be used for permanent magnet
synchronous motors only.
10.0%
2.0...100.0%
Value as a percentage of the nominal motor
frequency.
1 = 1%
Defines the minimum and maximum torque
boost time.
If torque boost time is less than 40% of
frequency acceleration time (see parameter
), then torque boost time is set at 40% of
frequency acceleration time.
20.0 s
0.0...60.0 s
Nominal motor time.
1 = 1%
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...