Fault tracing 329
5692 PU board
powerfail
Power unit power supply
failure.
Contact your local ABB
representative.
5693
Measurement
circuit DFF
Measurement circuit
fault.
Contact your local ABB
representative.
5695 Reduced run
Configured power units
not found.
Configure the power units.
5697
Charging
feedback
Charging feedback signal
missing.
Check the feedback signal
coming from the charging system
5698 Unknown PU fault The power unit logic
generated a fault which
is not known by
software.
Check the logic and software
compatibility.
50A0 Fan
Cooling fan stuck or
disconnected.
Check fan operation and
connection.
Replace fan if faulty.
6181
FPGA version
incompatible
Firmware and FPGA
versions are
incompatible.
Reboot the control unit (using
parameter
) or by cycling power. If the
problem persists, contact your
local ABB representative
6306 FBA A mapping
file
Fieldbus adapter A
mapping file read error.
Contact your local ABB
representative.
6481 Task overload
Internal fault.
Reboot the control unit (using
parameter
) or by cycling power. If the
problem persists, contact your
local ABB representative
6487 Stack overflow
Internal fault.
Reboot the control unit (using
parameter
) or by cycling power. If the
problem persists, contact your
local ABB representative
64A1 Internal file load
File read error.
Reboot the control unit (using
parameter
) or by cycling power. If the
problem persists, contact your
local ABB representative
64A3 Application
loading
Application file
incompatible or
corrupted.
Check the auxiliary code. See
actions for each code below.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...