134 Parameters
Defines the derivation time of the speed
controller.
Derivative action boosts the controller output if
the error value changes. The longer the
derivation time, the more the speed controller
output is boosted during the change. If the
derivation time is set to zero, the controller
works as a PI controller, otherwise as a PID
controller. The derivation makes the control
more responsive for disturbances. For simple
applications, derivative time is not normally
required and should be left at zero.
The speed error derivative must be filtered with a
low pass filter to eliminate disturbances.
The figure below shows the speed controller
output after an error step when the error remains
constant.
Note:
ABB recommends not to change the
default value. This can impact the MPPT
efficiency.
0.000
0.000…10.000 s Derivation time for speed controller.
1000 = 1
No.
Name/Value
Description
Def/
FbEq16
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time > 0
T
s
= Sample time period = 250 µs
Δ
e = Error value change between two samples
K
p
×
T
D
×
Δ
e
T
s
Controller output
e = Error value
Error value
Time
T
I
K
p
× e
K
p
× e
%
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...