330 Fault tracing
8006
Not enough memory for
the application.
Reduce the size of the
application. Reduce the number
of parameter mappings.
See the drive-specific log
generated by Automation Builder.
8007
The application contains
the wrong system library
version.
Update the system library or
reinstall Automation Builder.
See the drive-specific log
generated by Automation Builder.
8008
The application is empty. In Automation Builder, give a
“Clean” command and reload the
application.
8009
The application contains
invalid tasks.
In Automation Builder, check
application task configuration,
give a “Clean all” command, and
reload the application.
800A
The application contains
an unknown target
(system) library function.
Update the system library or
reinstall Automation Builder.
See the drive-specific log
generated by Automation Builder.
64A4 Rating ID fault
Rating ID load error.
Contact ABB.
64A6 Adaptive program Error running the
adaptive program.
Check the auxiliary code (format
XXYY ZZZZ).
“XX” specifies the number of the
state (00=base program) and
“YY” specifies the number of the
function block (0000=generic
error).
”ZZZZ” indicates the problem.
000A
Program corrupted or
block non-existent
Restore the template program or
download the program to the
drive.
000C
Required block input
missing
Check the inputs of the block.
000E
Program corrupted or
block non-existent
Restore the template program or
download the program to the
drive.
0011
Program too large.
Remove blocks until the error
stops.
0012
Program is empty.
Correct the program and
download it to the drive.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...