Parameters 207
Defines the “at setpoint” limits for speed control
of the drive.
When the difference between speed reference
and the speed feedback is smaller than
, the drive is considered to be “at
setpoint”. This is indicated by bit 8 of
.
50.00 rpm
0.00…
30000.00 rpm
Limit for “at setpoint” indication in speed
control.
1 = 1
Defines the “at setpoint” limits for frequency
control of the drive. When the absolute
difference between frequency reference and
actual frequency (
) is
smaller than
, the
drive is considered to be “at setpoint”. This is
indicated by bit 8 of
2.00 Hz
0.00…
1000.00 Hz
Limit for “at setpoint” indication in frequency
control.
10 = 1
Defines the trigger level for “above limit”
indication in speed control. When actual speed
exceeds the limit, bit 10 of
is set.
1500.00
rpm
0.00…
30000.00 rpm
“Above limit” indication trigger level for speed
control.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Speed feedback (rpm)
0 rpm
Speed ref
(rpm)
Speed reference (rpm)
Speed reference -
(rpm)
Drive at setpoint
bit 8 = 1)
(Hz)
0 Hz
Frequency ref
(Hz)
Frequency reference (Hz)
(Hz)
Drive at setpoint
bit 8 = 1)
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...