Parameters 185
Defines the thermal time constant for use with
the motor thermal protection model, defined as
the time to reach 63% of the nominal motor
temperature. See the motor manufacturer's
recommendations.
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
Selects how the drive reacts when the motor
reaches overload condition.
No action
None.
0
Warning only
warning.
1
Warning and
fault
warning and
2
Selects the motor overload class to be used.
Class 5
Class 5 relay trip class
0
Class 10
Class 10 relay trip class
1
Class 20
Class 20 relay trip class
2
Class 30
Class 30 relay trip class
3
Class 40
Class 40 relay trip class
4
No.
Name/Value
Description
Def/
FbEq16
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise