48 Program features
The pump cleaning sequence can have several positive direction speed steps in
one cleaning sequence.
When the negative speed is not allowed, the drive ignores phases 1…4.
Note:
Cleaning in a negative direction requires negative minimum
speed/frequency in parameter
Cleaning sequence steps
1. The pump system meets the triggering conditions as per the operating
mode (
) selected. At this condition, normal operation stops and the
drive uses the target time defined in parameter
reach zero speed.
2. Cleaning speed is defined by parameter
.
3. Initially, the pump runs in negative direction. The pump runs at cleaning
speed for the time defined by parameter
.
4. The pump decelerates to zero-speed. Time to zero speed is defined by
parameter
5. The pump is stopped until parameter
is elapsed.
6. The pump accelerates the pump speed to positive direction. See parameter
.
7. The pump runs at the positive cleaning speed. See parameter
.
8. The pump decreases the pump speed back to zero defined by parameter
.
Normal operation
Time
1
2
3
4
5
6
7
8
9
10
Normal operation
2
3
4
5
6
7
8
9
Sequence Parameter
Sequence Parameter
1
6
2
7
3
8
4
9
5
10
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...