Program features 51
Time scheduled pump cleaning
Time scheduled pump cleaning allows you to clean the pump at the desired
time. When the time scheduled pump cleaning is enabled and the present time
is equal to the user mentioned time, the normal operation stops and the pump
cleaning starts automatically.
You can enter a maximum of five different times of a day in the parameters
....
and schedule the pump
cleaning. Setting the time in ascending order or descending order is not
mandatory and you can set any time as per your need. Cleaning is activated only
if the drive start command is already active i.e. drive is in running state.
If drive is not running at the defined time, the drive skips the cleaning schedule
of that particular time. If a pump cleaning operation is ongoing and any of the
remaining defined time matches the present time, the cleaning operation does
not stop and ignores the pump cleaning trigger. After the pump cleaning, the
normal pump operation starts.
Notes:
• A warning
is generated, if the system time is not set
properly and time scheduled pump is activated.
and the time scheduled pump
cleaning is running based on the set time, the drive does not generate the
Settings
(page
Dry run protection
The dry run protection function automatically detects and avoids running of a
pump with no flow of water in the pump. The dry run protection can be
activated through one of the following methods:
• Using DI
• Using minimum load current
Dry run protection using DI
The dry run protection using DI (
= any DI), detects the dry
run condition of the pump based on the digital signals received from the
sensors. The drive trips on fault
whenever the sensor detects
the dry run condition and sends the digital input value true to the drive.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...