Fault tracing 319
0005
Motor could not
decelerate with full
autotune torque.
Decrease the torque step
(parameter
) or the speed
step (parameter
0006
Autotune could not write
a parameter.
Run the drive one more time.
0007
Drive was ramping down
when the autotune was
activated.
Run the drive to the set point
and start the autotune one more
time.
0008
Drive was ramping up
when the autotune was
activated.
Wait until the drive reaches the
set point and start autotune.
0009
Drive was running
outside of autotune
speed limits during the
autotune activation.
Check the limits, set the correct
setpoint and repeat the
autotune.
B5F6 Identification run
Motor ID run completed
successfully.
Informative warning.
B5A0 STO event
Programmable
event:
Safe torque off function
is active, ie. safety circuit
signal(s) connected to
connector STO is lost.
Check safety circuit
connections. For more
information, see chapter
The
Safe torque off function
in the
Hardware manual
of the drive
and description of parameter
(page
D505 Max cleaning
warning
Programmable
warning:
Maximum number of
cleanings are reached in
defined time. The Pump
cleaning is unable to
clean the pump and
hence, manual cleaning is
required.
Check the pump for blockages.
Clean the pump manually if
needed.
Check parameters
D506 Pump cleaning not
possible
Pump cleaning not
started as the drive is not
in remote control.
Set the drive to remote control
mode.
D507 Pump cleaning
needed
Dirt detection indicates
that the pump needs
cleaning but automatic
pump cleaning is not
allowed.
Perform pump cleaning
manually.
Start pump cleaning by
to Start cleaning
now.
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...