244 Parameters
Enables/disables the pump cleaning.
Not active
Pump cleaning is not active.
0
Start cleaning
now
Starts pump cleaning immediately.
1
DI4
Starts pump cleaning when DI4 goes high.
2
DI5
Starts pump cleaning when DI5 goes high.
3
DI6
Starts pump cleaning when DI6 goes high.
4
Source selection (see
on
page
-
Defines the constant time interval between
cleaning cycles.
Note
: This parameter is used only when cleaning
is triggered by time interval.
02 00:00
00 00:00…
45:12:15
Time interval in format DD HH:MM (day
hour:min).
-
Defines the number of cycles performed in
cleaning program.
For example, 1 cycle = 1 f 1 reverse step.
3
1...65535
Value range
Defines the speed/frequency step size in pump
cleaning.
Cleaning speed step is same for positive and
negative directions.
Note:
If you have disabled the negative rotation
direction by speed limits, the pump cleaning
does not operate in the negative direction.
2400
0...3000 rpm
Cleaning speed/frequency value.
1 = 1 rpm
Defines the time required for the drive to reach
cleaning speed set by parameter
3.000
0.000...60.000 s Time
1 = 1s
Defines the time required for the drive to reach
zero speed from the cleaning speed set by
parameter
.
3.000
0.000...60.000 s Time
1 = 1s
Defines the pump cleaning time in a cycle when
the drive is running at cleaning speed set by
.
10.000
0.000...
1000.000 s
Time
1 = 1s
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...