178 Parameters
Selects the source from which measured
temperature 1 is read.
Usually this source is from a sensor connected to
the motor controlled by the drive, but it could be
used to measure and monitor a temperature
from other parts of the process as long as a
suitable sensor is used as per the selection list.
Disabled
None. Temperature monitoring function 1 is
disabled.
0
Estimated
temperature
Estimated motor temperature (see parameter
).
The temperature is estimated from an internal
drive calculation. It is important to set up the
ambient temperature of the motor in
.
1
KTY84 analog
I/O
KTY84 sensor connected to the analog input
selected by parameter
and an analog output. The analog input
can be from the standard I/O or from an
extension module
The following settings are required:
• Set the hardware jumper or switch related to
the analog input to
U
(voltage). Any change
must be validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
to
(volt).
• In parameter group
, set the
source selection parameter of the analog
output to
The analog output feeds a constant current
through the sensor. As the resistance of the
sensor increases along with its temperature, the
voltage over the sensor increases. The voltage is
read by the analog input and converted into
degrees.
2
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...