150 Parameters
Defines, together with
and
, the maximum
allowed frequency of the motor. If the speed
(
) exceeds the
frequency limit defined by parameter
by more than the value of this parameter,
the drive trips on the
fault.
WARNING!
This function only supervises
the speed in scalar motor control mode.
The function is not effective in vector motor
control mode.
Example:
If the maximum speed is 40 Hz and
speed trip margin is 10 Hz, the drive trips at
50 Hz.
15.00 Hz
0.00…
10000.00 Hz
Overfrequency trip margin.