140 Parameters
Defines the minimum allowed speed.
WARNING!
This value must not be higher
WARNING!
In speed control mode only. In
frequency control mode, use frequency
limits (
).
Note:
Set the value to 0 to prevent the pump to
run in negative directive.
-3000.00
rpm
-30000.00…
30000.00 rpm
Minimum allowed speed.
1 = 1
Defines the maximum allowed speed.
WARNING!
This value must not be lower
WARNING!
In speed control mode only. In
frequency control mode, use frequency
limits (
).
3000.00
rpm
-30000.00…
30000.00 rpm
Maximum speed.
1 = 1
Defines the minimum allowed frequency.
WARNING!
This value must not be higher
WARNING!
in frequency control mode only.
-300.00 Hz
-500.00…
500.00 Hz
Minimum frequency.
10 = 1
Defines the maximum allowed frequency.
WARNING!
This value must not be lower
WARNING!
In frequency control mode only.
300.00 Hz
-500.00…
500.00 Hz
Maximum frequency.
10 = 1
Defines the maximum allowed drive current.
3.24 A
0.00…3.24 A
Maximum drive current.
1 = 1 A
Defines a minimum torque limit for the drive (in
percent of nominal motor torque).
-300.0%
-1600.0…0.0%
Minimum torque limit 1.
10 = 1
Defines a maximum torque limit for the drive (in
percent of nominal motor torque).
300.0%
0.0…1600.0%
Maximum torque 1.
10 = 1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...