336 Fault tracing
80B5 Signal supervision
6
(Editable message
text)
Programmable fault:
Fault generated by the
signal supervision
function 6.
Check the source of the fault
(parameter
9081 External fault 1
(Editable message
text)
Programmable fault:
Fault in external device 1. Check the external device.
Check setting of parameter
.
9082 External fault 2
(Editable message
text)
Programmable fault:
Fault in external device 2. Check the external device.
Check setting of parameter
.
9083 External fault 3
(Editable message
text)
Programmable fault:
Fault in external device 3. Check the external device.
Check setting of parameter
.
9084 External fault 4
(Editable message
text)
Programmable fault:
Fault in external device 4. Check the external device.
Check setting of parameter
.
9085 External fault 5
(Editable message
text)
Programmable fault:
Fault in external device 5. Check the external device.
Check setting of parameter
.
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...