Startup, control with I/O and ID run 21
Refer to the motor nameplate for the following nominal value settings of the motor.
Enter the values exactly as shown on the motor nameplate.
Example of a nameplate of an induction (asynchronous) motor:
Select the motor type.
Check that the motor data is correct. Values
are predefined on the basis of the drive size
but you should verify that they correspond to
the motor.
Start with the motor nominal current.
If you have to change the value, go to the edit
view of the selected row by pressing
(when this symbol is shown at the end of the
row).
Set the correct value:
• Use
and
to move the cursor left and
right.
• Use
and
to change the value.
Press
(
Save
) to accept the new setting,
or press
(
Cancel
) to go back to the
previous view without making changes.
Continue to check/edit the nominal values
and select scalar or vector control mode.
Motor nominal cos
Φ
and nominal torque are
optional.
Roll down with
to see the last row in the
view.
After editing the last row, the control panel
goes to the next view.
To go directly to the next view, press
(
Next
).
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...