322 Fault tracing
Fault messages
Code
(hex)
Fault / Aux. code
(
aux code visible only on
assistant control panel
and drive composer)
Cause
What to do
1080 Backup/Restore
timeout
Panel or PC tool has
failed to communicate
with the drive when
backup was being made
or restored.
Request backup or restore again.
1081
Rating ID fault
Drive software is not able
to read the rating ID of
the drive.
Reset the fault to make the drive
try to reread the rating ID.
If the fault reappears, cycle the
power to the drive. You may have
to be repeat this. If the fault
persists, contact your local ABB
representative.
2281
Calibration
Measured offset of
output phase current
measurement or
difference between
output phase U2 and W2
current measurement is
too great (the values are
updated during current
calibration).
Try performing the current
calibration again.
If the fault persists, contact your
local ABB representative.