Fault tracing 315
0002
Relay output 2
Change the control board or
stop using relay output 2.
0003
Relay output 3
Change the control board or
stop using relay output 3.
A8A0 AI supervision
Analog signal is beyond
limits.
Check the signal level, input
wiring, and the defined limits.
A8A1 RO life warning
The relay has changed
states more than the
recommended number of
times.
Change the control board or
stop using the relay output.
0001
Relay output 1
Change the control board or
stop using relay output 1.
0002
Relay output 2
Change the control board or
stop using relay output 2.
0003
Relay output 3
Change the control board or
stop using relay output 3.
A8A2 RO toggle warning The relay output is
changing states faster
than recommended, eg.
if a fast changing
frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
Replace the signal connected to
the relay output source with a
less frequently changing signal.
0001
Relay output 1
Select a different signal with
parameter
.
0002
Relay output 2
Select a different signal with
parameter
.
0003
Relay output 3
Select a different signal with
parameter
.
A8B0 Signal supervision
1
(Editable message
text)
Programmable
warning:
Warning generated by
the signal supervision
function 1.
Check the source of the warning
).
Code
(hex)
Warning / Aux.
code
(
aux code visible
only on assistant
control panel and drive
composer)
Cause
What to do
1 – AI1 less minimum
3 – AI2 less minimum
2 – AI1 greater maximum
4 – AI2 greater maximum
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...