Parameters 243
Displays the cleaning count. Cleaning count
increments by one, when the sequence of
cleaning cycles are completed.
For example, if
is
set as 3, the pump cleaning completes after three
cycles of reverse and forward motions of the
pump and the cleaning count changes to 1.
0
0...
42994967000
Total cleaning count.
1 = 1
Enables the pump cleaning action.
Off
Pump cleaning is disabled.
0
Cleaning
Pump cleaning is started based on triggers.
1
Warning only
Generates
warning
message based on triggers.
2
Enables/disables the pump cleaning sequence
for the drive, and defines the triggering
conditions.
Note:
If DI1 remains On after cleaning is finished,
no cleaning sequence is started. The drive starts
cleaning on next start, if the trigger signal is On
when motor is started.
0b0000
0000h…FFFFh
Pump cleaning triggers,
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Reserved
1
Every start
Cleaning starts at every start.
2
Every stop
Cleaning starts at every stop.
3...5
Reserved
6
Fixed time interval
Time interval defined by parameter
.
7
Combined timer1
Combined timer 1 of timed functions starts
cleaning.
8…9
Reserved
10
Supervision 1
Cleaning sequence starts when Supervision 1 is
high.
11
Supervision 2
Cleaning sequence starts when Supervision 2 is
high.
12
Supervision 3
Cleaning sequence starts when Supervision 3 is
high.
13
DI4
Cleaning sequence starts when DI4 is high.
14
DI5
Cleaning sequence starts when DI5 is high.
15
DI6
Cleaning sequence starts when DI6 is high.
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...