152 Parameters
32
Configuration of signal supervision functions
1…6.
Six values can be chosen to be monitored; a
warning or fault is generated whenever
predefined limits are exceeded.
See also section
(page
Signal supervision status word.
Indicates whether the values monitored by the
signal supervision functions are within or outside
their respective limits.
Note:
This word is independent of the drive
actions defined by parameters
,
,
.
0b000
0b0000…
0b1111
Signal supervision status word.
1 = 1
Selects the mode of signal supervision function 1.
Determines how the monitored signal (see
parameter
) is compared to its lower and
upper limits (
and
respectively). The
action to be taken when the condition is fulfilled
is selected by
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever signal is below
'Supervision low' limit - 0.5 * hysteresis.
Action is deactivated whenever signal is above
'Supervision low' limit + 0.5 * hysteresis.
1
High
Action is taken whenever signal is above
Supervision High limit + 0.5 * hysteresis. Action is
deactivated whenever signal is below
Supervision High limit - 0.5 * hysteresis.
2
Abs low
Action is taken whenever absolute value of signal
is below absolute value of Supervision Low limit -
0.5 * hysteresis. Action is deactivated whenever
absolute value of signal is above absolute value
of Supervision Low limit + 0.5 * hysteresis.
3
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Supervision 1 active
1 = Signal selected by
is outside its limits.
1
Supervision 2 active
1 = Signal selected by
is outside its limits.
2
Supervision 3 active 1 = Signal selected by
is outside its limits.
3
Supervision 4 active 1 = Signal selected by
is outside its limits.
4
Supervision 5 active 1 = Signal selected by
is outside its limits.
5
Supervision 6 active 1 = Signal selected by
is outside its limits.
6…15 Reserved
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...