![YASKAWA U1000 Series Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114072.webp)
3.2 Standard Connection Diagram
72
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
<4> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply.
<5> For control modes that do not use a motor speed feedback signal, PG option card wiring is not necessary.
<6> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Use jumper S3 to select
the sink mode for the use of an internal power supply or the source mode for the use of an external power supply.
<7> Wire the fault relay output separately from the main circuit power supply and other power lines.
<8> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terV, -V, and AC, as
this can cause erroneous operation or damage the drive.
<9> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<10> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
<11> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as
a feedback-type of signal.
<12> The sink/source setting for the Safe Disable input is the same as with the sequence input. Jumper S3 has the drive set for an external power
supply. When not using the Safe Disable input feature, remove the jumper shorting the input and connect an external power supply. Refer to
for instructions.
<13> Models CIMR-U
E
and
W
have EMC filter switch. Models CIMR-U
4
0477 to 4
0590 with a stand-alone EMC
filter do not have the EMC filter switch.
<14> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
<15> Models CIMR-U
P
and
W
have terminals 24, 0, and FE. The main circuit power supply can be turned off separately
even when power is supplied to the control circuit.
SIEP_C710636_02B_1_0.book 72 ページ 2015年11月25日 水曜日 午後4時56分