B.3 Parameter Table
496
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
◆
H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
■
H1: Multi-Function Digital Inputs
F7-19
(3F7H)
EtherNet/IP Torque Scaling Factor
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-20
(3F8H)
EtherNet/IP Power Scaling Factor
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-21
(3F9H)
EtherNet/IP Voltage Scaling Factor
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-22
(3FAH)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-23 to
F7-27
(3FBH to
3FFH),
F7-28 to
F7-32
(370H to
374H)
Dynamic Output Assembly
Parameters
Parameters used in Output Assembly 116. Each parameter contains a MEMOBUS/Modbus
address. The value received for Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means that the value
received for Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
Default: 0
–
F7-33 to
F7-42
(375H to
37EH)
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each parameter contains a MEMOBUS/Modbus
address. The value sent for Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means that the value
sent for Input Assembly 166 is not defined by the user, therefore the option default register
value will be returned.
Refer to Ethernet/IP Technical Manual for definitions of the default MEMOBUS/Modbus
registers.
Default: 0
–
<44> Cycle power for setting changes to take effect.
<45> If F7-13 is set to 0, then all IP Addresses (as defined with parameters F7-01 to F7-04) must be unique.
<46> Set F7-01 to F7-12 when F7-13 is set to 0.
<47> Set F7-15 when F7-14 is set to 0 or 2.
No.(Addr.)
Name
Description
Setting
Page
H1-01
(438H)
<31> Value in parenthesis is the default setting when a 3-wire initialization is performed (A1-03 = 3330).
Multi-Function Digital Input
Terminal S1 Function Selection
Assigns a function to the multi-function digital inputs.
Refer to
H1 Multi-Function Digital Input Selections on page 497
for a description of setting
values.
Note:
Unused terminals should be set to F.
Default: 40 (F)
Min: 1
Max: 9F
H1-02
(439H)
Multi-Function Digital Input
Terminal S2 Function Selection
Default: 41 (F)
Min: 1
Max: 9F
H1-03
(400H)
Multi-Function Digital Input
Terminal S3 Function Selection
Default: 24
Min: 0
Max: 9F
H1-04
(401H)
Multi-Function Digital Input
Terminal S4 Function Selection
Default: 14
Min: 0
Max: 9F
H1-05
(402H)
Multi-Function Digital Input
Terminal S5 Function Selection
Default: 3 (0)
Min: 0
Max: 9F
H1-06
(403H)
Multi-Function Digital Input
Terminal S6 Function Selection
Default: 4 (3)
Min: 0
Max: 9F
H1-07
(404H)
Multi-Function Digital Input
Terminal S7 Function Selection
Default: 6 (4)
Min: 0
Max: 9F
H1-08
(405H)
Multi-Function Digital Input
Terminal S8 Function Selection
Default: 8
Min: 0
Max: 9F
No.(Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes