![YASKAWA U1000 Series Скачать руководство пользователя страница 532](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114532.webp)
532
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
B.4 Control Mode Dependent Parameter Default Values
B.4 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2).
These parameters are initialized to the shown values if the control mode is changed.
◆
A1-02 (Motor 1 Control Mode) Dependent Parameters
Table B.2 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
V/f w/PG (1)
OLV (2)
CLV (3)
b2-01
DC Injection Braking Start Frequency
0.0 to 10.0
0.1
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
b2-04
DC Injection Braking Time at Stop
0.00 to 10.00
0.01 s
0.50
0.50
0.50
0.50
b3-01
Speed Search Selection at Start
0 or 1
–
0
1
0
–
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.00 to 6.00
–
b3-14
Bi-Directional Speed Search Selection (Speed
Estimation Type, Speed Estimation 2 Type,
Current Detection 3 Type)
0 or 1
–
1
0
1
–
b3-24
Speed Search Method Selection
1 to 4
–
2
2
2
b5-15
PID Sleep Function Start Level
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
b6-01
Dwell Reference at Start
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
b6-03
Dwell Reference at Stop
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
b8-01
Energy Saving Control Selection
0 or 1
–
0
0
0
0
b8-02
Energy Saving Gain
0.0 to 10.0
0.1
–
–
0.7
1.0
b8-03
Energy Saving Control Filter Time Constant
0.00 to 10.00
0.01 s
–
–
0.50
0.01
C1-11
Accel/Decel Time Switching Frequency
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
C2-01
S-Curve Time at Accel Start
0.00 to 10.00
0.01 s
0.20
0.20
0.20
0.20
C3-01
Slip Compensation Gain
0.0 to 2.5
0.1
0.0
–
1.0
1.0
C3-02
Slip Compensation Primary Delay Time
0 to 10000
1 ms
2000
–
200
–
C4-01
Torque Compensation Gain
0.00 to 2.50
0.01
1.00
1.00
1.00
–
C4-02
Torque Compensation Primary Delay Time
0 to 10000
1 ms
200
200
20
–
C5-01
ASR Proportional Gain 1
0.00 to 300.00
0.01
–
0.20
–
20.00
C5-02
ASR Integral Time 1
0.000 to 10.000
0.001 s
–
0.200
–
0.500
C5-03
ASR Proportional Gain 2
0.00 to 300.00
0.01
–
0.02
–
20.00
C5-04
ASR Integral Time 2
0.000 to 10.000
0.001 s
–
0.050
–
0.500
C5-06
ASR Primary Delay Time Constant
0.000 to 0.500
0.001 s
–
–
–
0.004
C5-07
ASR Gain Switching Frequency
0.0 to 400.0
0.1
–
–
–
0.0 Hz
C6-02
Carrier Frequency Selection
0 to 4, F
–
1
1
1
d3-01
Jump Frequency 1
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-02
Jump Frequency 2
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-03
Jump Frequency 3
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
d3-04
Jump Frequency Width
0.0 to 20.0
0.1
1.0 Hz
1.0 Hz
1.0 Hz
1.0 Hz
d5-02
Torque Reference Delay Time
0 to 1000
1 ms
–
–
–
0
E1-04
Maximum Output Frequency
40.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-05
Maximum Voltage
0.0 to 255.0
0.1 V
200
200
200
200
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
60.0
60.0
60.0
60.0
E1-07
Middle Output Frequency
0.0 to 400.0
0.1 Hz
3.0
3.0
0.0
E1-08
Middle Output Frequency Voltage
0.0 to 255.0
0.1 V
15.0
15.0
11.0
0.0
E1-09
Minimum Output Frequency
0.0 to 400.0
0.1 Hz
1.5
0.5
0.0
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0
0.1 V
9.0
9.0
2.0
0.0
F1-01
PG 1 Pulses Per Revolution
0 to 60000
1 ppr
–
600
–
600
F1-05
PG 1 Rotation Selection
0 or 1
–
–
0
–
0
F1-09
Overspeed Detection Delay Time
0.0 to 2.0
0.1 s
–
1.0
–
0.0
L1-01
Motor Overload Protection Selection
0 to 6
–
1
1
1
1
L3-36
Vibration Suppression Gain during Acceleration
(with Current Limit)
0.0 to 100.0
–
10.0
10.0
20.0
–
L3-41
Vibration Suppression Gain during Deceleration
(with Current Limit)
0.0 to 100.0
–
10.0
10.0
20.0
–
L4-01
Speed Agreement Detection Level
0.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-02
Speed Agreement Detection Width
0.0 to 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L4-03
Speed Agreement Detection Level (+/-)
-400.0 to 400.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-04
Speed Agreement Detection Width (+/–)
0.0 to 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L8-18
Software Current Limit Selection
0 to 1
–
0
0
L8-38
Carrier Frequency Reduction Selection
0 to 2
–
L8-40
Carrier Frequency Reduction Off Delay Time
0.00 to 2.00
0.01 s
0.50
0.50
0.50
0.50
o1-03
Digital Operator Display Selection
0 to 3
–
0
0
0
0
o1-04
V/f Pattern Display Unit
0 or 1
–
–
–
–
0
SIEP_C710636_02B_1_0.book 532 ページ 2015年11月25日 水曜日 午後4時56分