![YASKAWA U1000 Series Скачать руководство пользователя страница 161](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114161.webp)
4.7 Auto-Tuning
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
161
St
ar
t-
Up Pr
ogr
ammi
ng
&
O
p
er
at
io
n
4
■
Starting Auto-Tuning
WARNING!
Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death
or serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING!
Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE:
Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in
improper operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Enter the required information from the motor nameplate. Press
to proceed to the Auto-Tuning start display.
Note:
These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
◆
Parameter Settings during Induction Motor Auto-Tuning: T1
The T1-
parameters are used to set the Auto-Tuning input data for induction motor tuning.
Note:
For motors that are to be operated in the field weakening range, first perform the Auto-Tuning with the base data. After
Auto-Tuning is complete, change the maximum frequency E1-04 to the desired value.
■
T1-00: Motor 1/Motor 2 Selection
Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input is set for function H1-
= 16.
This parameter is not displayed if motor 1/2 switching is disabled.
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E1-
and E2-
for motor 1.
Setting 2: Motor 2
Auto-Tuning automatically sets parameters E3-
and E4-
for motor 2. Make sure that motor 2 is connected to the
drive for Auto-Tuning.
Step
Display/Result
1.
After entering the data listed on the motor nameplate, press
to confirm.
2.
Press
to activate Auto-Tuning. The drive begins by injecting current into the motor for about 1 min,
and then starts to rotate the motor.
Note:
The first digit on the display indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The
second digit indicates the type of Auto-Tuning being performed.
3.
Auto-Tuning finishes in approximately one to two minutes.
No.
Name
Setting Range
Default
T1-00
Motor 1/Motor 2 Selection
1 or 2
1
- A.TUNE -
0.00 Hz/ 0.00A
Tuning Ready ?
DRV
Auto-Tuning
ESC
FWD
Press RUN key
Rdy
- A.TUNE -
X.XX Hz/ X.XXA
DRV
Tune Proceeding
Rdy
FWD
- MODE -
End
Tune Successful
DRV
FWD
RESET
SIEP_C710636_02B_1_0.book 161 ページ 2015年11月25日 水曜日 午後4時56分