C7-56: Power Factor Control Selection
Power factor control improves the input power supply power factor according to the operating conditions. This parameter
rarely requires adjustment, but may be enabled to improve the power factor in the low output region.
Power factor control is not suitable for applications with frequent load fluctuations. This function is disabled in High
Output Voltage Mode (C7-60 = 1).
0: Power Factor Control Disabled
1: Power Factor Control Enabled
■
C7-60: Output Voltage Limit Mode Selection
Sets the mode to limit the output voltage.
Set this parameter to 0 (Harmonic suppression priority mode) to give priority to harmonic suppression. The maximum
output voltage is automatically limited to suppress harmonics.
Set this parameter to 1 (High output voltage mode) to give priority to the output voltage over harmonic suppression. The
effectiveness of harmonic suppression will be reduced because the maximum output voltage will be used.
Setting 0: Harmonic Suppression Priority Mode
Setting 1: High Output Voltage Mode
No.
Parameter Name
Setting Range
Default
C7-56
Power Factor Control Selection
0, 1
0
No.
Parameter Name
Setting Range
Default
C7-60
Output Voltage Limit Mode Selection
0, 1
1