5.10 o: Operator Related Settings
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
331
5
5.10 o: Operator Related Settings
These parameters are for controlling the various functions, features, and display of the digital operator.
◆
o1: Digital Operator Display Selection
These parameters determine how data appears on the operator display.
■
o1-01: Drive Mode Unit Monitor Selection
When o1-02 is set to 5, any U monitors can be displayed. This parameter will select the monitors. Pressing the up arrow
key will display the following data: speed reference
→
rotational direction
→
output speed
→
output current
→
o1-01
selection.
Parameter o1-01 selects the content of the last monitor in this sequence. This is done by entering the “1
”part of
“U1-
”. Certain monitors are not available in some control modes.
There is no effect like this on an LCD operator.
■
o1-02: User Monitor Selection after Power Up
Selects which monitor parameter is displayed upon power up.
Refer to U: Monitor Parameters on page 338
for a list of
monitors.
Setting 1: Frequency reference (U1-01)
Setting 2: Motor direction
Setting 3: Output frequency (U1-02)
Setting 4: Output current (U1-03)
Setting 5: User-selected monitor (set by o1-01)
■
o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units, then set
parameters o1-10 and o1-11.
Setting 0: 0.01 Hz units
Setting 1: 0.01% units (100% = max. output frequency)
Setting 2: min
-1
units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)
Set the value use for the maximum frequency reference to o1-10. The placement of the decimal point in this number
should be set to o1-11.
For example, to have the maximum output frequency displayed as “100.00”, set the o1-10 = 1000 and o1-11 = 2 (i.e.,
1000 with 2 decimal points).
Note: 1.
Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-05: motor speed
U1-16: output frequency after soft starter (accel/decel ramp generator)
d1-01 to d1-17: frequency references
2.
Setting o1-03 to 2 requires that the number of motor poles be entered to E2-04, E4-04, and E5-04.
No.
<1> U2-
and U3-
parameters cannot be selected.
Name
Setting Range
Default
o1-01
Drive Mode Unit Monitor Selection
104 to 914
U1-04 (Control Mode) to U9-14 (Power
Monitor)
106 (U1-06)
No.
Name
Setting Range
Default
o1-02
User Monitor Selection after Power Up
1 to 5
1
No.
Name
Setting Range
Default
o1-03
Digital Operator Display Selection
0 to 3
Determined by A1-02