B.3 Parameter Table
492
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
F5: Digital Output Card Settings (DO-A3)
■
F6: Communication Option Card
(SI-C3, SI-EM3, SI-EN3, SI-ET3, SI-N3, SI-P3, SI-S3, SI-T3, and SI-W3)
F6-01 through F6-03 and F6-06 through F6-08 are common settings used for CC-Link, CANopen, DeviceNet, Ethernet/
IP, PROFIBUS-DP, MECHATROLINK-II, MECHATROLINK-III, Modbus TCP/IP, and LONWORKS option cards.
Other parameters in the F6 group are used for communication protocol specific settings.
For more details on a specific option card, refer to the instruction manual for the option card.
F4-05
(395H)
Terminal V1 Monitor Bias
Sets the amount of bias added to the voltage output via terminal V1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
F4-06
(396H)
Terminal V2 Monitor Bias
Sets the amount of bias added to the voltage output via terminal V2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
F4-07
(397H)
Terminal V1 Signal Level
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min: 0
Max: 1
F4-08
(398H)
Terminal V2 Signal Level
Default: 0
Min: 0
Max: 1
No.(Addr.)
Name
Description
Setting
Page
F5-01
(399H)
Terminal P1-PC Output Selection
Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
Default: 0
Min: 0
Max: 192
F5-02
(39AH)
Terminal P2-PC Output Selection
Default: 1
Min: 0
Max: 192
F5-03
(39BH)
Terminal P3-PC Output Selection
Default: 2
Min: 0
Max: 192
F5-04
(39CH)
Terminal P4-PC Output Selection
Default: 4
Min: 0
Max: 192
F5-05
(39DH)
Terminal P5-PC Output Selection
Default: 6
Min: 0
Max: 192
F5-06
(39EH)
Terminal P6-PC Output Selection
Default: 37
Min: 0
Max: 192
F5-07
(39FH)
Terminal M1-M2 Output Selection
Default: F
Min: 0
Max: 192
F5-08
(3A0H)
Terminal M3-M4 Output Selection
Default: F
Min: 0
Max: 192
F5-09
(3A1H)
DO-A3 Output Mode Selection
0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through F5-08.
Default: 0
Min: 0
Max: 2
No.(Addr.)
Name
Description
Setting
Page
F6-01
(3A2H)
Communications Error Operation
Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
F6-02
(3A3H)
External Fault from Comm. Option
Detection Selection
0: Always detected
1: Detection during run only
Default: 0
Min: 0
Max: 1
F6-03
(3A4H)
External Fault from Comm. Option
Operation Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
F6-04
(3A5H)
bUS Error Detection Time
Set the delay time for error detection if a bus error occurs.
Default: 2.0 s
Min: 0.0 s
Max: 5.0 s
–
No.(Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes