5.2 b: Application
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
189
5
■
b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being
used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and
Auto-Tuning Mode). If required by the application, set b1-08 to allow the drive to run while in the Programming Mode.
Setting 0: Disabled
A Run command is not accepted while the digital operator is in the Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
■
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
Setting 0: Standard phase order
Setting 1: Switched phase order (A1-02 = 0, 1, 2, 3, 5, 6)
■
b1-15: Frequency Reference Selection 2
This parameter is used to set the source for the secondary frequency reference. b1-15 is enabled when H1-
= 2 and
the terminal is closed.
Refer to Setting 2: External reference 1/2 selection on page 267
for details.
■
b1-16: Run Command Selection 2
This parameter is used to set the source for the secondary run command. b1-16 is enabled when H1-
= 2 and the
Refer to Setting 2: External reference 1/2 selection on page 267
for details.
■
b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up will start the drive
or not.
Setting 0: Run command at power up is not accepted
The Run command has to be cycled to start the drive.
Note:
For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is
issued at power up, the RUN indicator LED will flash quickly.
No.
Parameter Name
Setting Range
Default
b1-08
Run Command Selection while in Programming Mode
0 to 2
0
No.
Parameter Name
Setting Range
Default
b1-14
Phase Order Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
b1-15
Frequency Reference Selection 2
0 to 4
0
No.
Parameter Name
Setting Range
Default
b1-16
Run Command Selection 2
0 to 3
0
No.
Parameter Name
Setting Range
Default
b1-17
Run Command at Power Up
0 or 1
0