4.7 Auto-Tuning
166
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
T2-12: PM Motor q-Axis Inductance
Enter the q axis inductance per motor phase.
■
T2-13: Induced Voltage Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
Setting 0: mV (min
-1
)
Setting 1: mV (rad/s)
Note:
If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2 (for PM Motors)), and will automatically
set E5-09 (Motor Induction Voltage Constant 1 (Ke) (for PM Motors)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09
and will automatically set E5-25 to 0.0.
■
T2-14: PM Motor Induced Voltage Constant (Ke)
Enter the motor induced voltage constant (Ke).
■
T2-15: Pull-In Current Level for PM Motor Tuning
Sets the amount of pull-in current used to tune the d-axis and q-axis inductance. Set as a percentage of the motor rated
current.
■
T2-16: PG Number of Pulses Per Revolution for PM Motor Tuning
Enter the number of pulses from the PG encoder per motor rotation. Set the actual number of pulses for one full motor
rotation.
■
T2-17: Encoder Z-Pulse Offset (
Δθ
)
Sets the amount of compensation or offset in 0.1 degree units in order to fine-tune the home position. If the amount of
offset needed for the Z pulse is unknown or if the PG encoder is replaced, perform Z pulse tuning.
No.
Name
Setting Range
Default
T2-12
PM Motor q-Axis Inductance
0.00 to 600.00 mH
Depending on T2-02
No.
Name
Setting Range
Default
T2-13
Induced Voltage Constant Unit Selection
0, 1
1
No.
Name
Setting Range
Default
T2-14
PM Motor Induced Voltage Constant (Ke)
0.0 to 2000.0
Depending on T2-02
No.
Name
Setting Range
Default
T2-15
Pull-In Current Level for PM Motor Tuning
0 to 120%
30%
No.
Name
Setting Range
Default
T2-16
PG Number of Pulses Per Revolution for PM Motor Tuning
1 to 15000 ppr
1024 ppr
No.
Name
Setting Range
Default
T2-17
Encoder Z-Pulse Offset (
Δθ
)
-180.0 to 180.0 deg
0.0 deg