![YASKAWA U1000 Series Скачать руководство пользователя страница 494](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114494.webp)
B.3 Parameter Table
494
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
F6-36
(3D1H)
CANopen Communication Speed
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Default: 6
Min: 0
Max: 8
–
F6-50
(3C1H)
DeviceNet MAC Address
Selects the drives MAC address.
Default: 0
Min: 0
Max: 64
–
F6-51
(3C2H)
DeviceNet Communication Speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Default: 0
Min: 0
Max: 4
–
F6-52
(3C3H)
DeviceNet PCA Setting
Sets the format of the data set from the DeviceNet master to the drive.
Default: 21
Min: 0
Max: 255
–
F6-53
(3C4H)
DeviceNet PPA Setting
Sets the format of the data set from the drive to the DeviceNet master.
Default: 71
Min: 0
Max: 255
–
F6-54
(3C5H)
DeviceNet Idle Mode Fault
Detection
0: Enabled
1: Disabled, no fault detection
Default: 0
Min: 0
Max: 1
–
F6-55
(3C6H)
DeviceNet Baud Rate Monitor
Used to verify the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
Default: 0
Min: 0
Max: 2
–
F6-56
(3D7H)
DeviceNet Speed Scaling
Sets the scaling factor for the speed monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-57
(3D8H)
DeviceNet Current Scaling
Sets the scaling factor for the output current monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-58
(3D9H)
DeviceNet Torque Scaling
Sets the scaling factor for the torque monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-59
(3DAH)
DeviceNet Power Scaling
Sets the scaling factor for the power monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-60
(3DBH)
DeviceNet Voltage Scaling
Sets the scaling factor for the voltage monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-61
(3DCH)
DeviceNet Time Scaling
Sets the scaling factor for the time monitor in DeviceNet.
Default: 0
Min: -15
Max: 15
–
F6-62
(3DDH)
DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications.
Default: 0
Min: 0
Max: 10
–
F6-63
(3DEH)
DeviceNet Network MAC ID
Saves and monitors the settings 0 to 63 of F6-50 (DeviceNet MAC Address).
Default: 0
Min: 0
Max: 63
–
F6-64 to
F6-71
(3DFH to
3C8H)
Reserved
Reserved for Dynamic I/O Assembly Parameters.
–
–
<3> Parameter setting value is not reset to the default value when the drive is initialized.
No.(Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710636_02B_1_0.book 494 ページ 2015年11月25日 水曜日 午後4時56分