![YASKAWA U1000 Series Скачать руководство пользователя страница 553](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114553.webp)
B.7 Parameters that Change with the Motor Code Selection (for PM Motors)
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
553
t
B
Table B.21 200 V, 1450 min
-1
Type YASKAWA SST4 Series IPM Motor
No.
Name
Unit
Default Settings
E5-01
Motor Code Selection (for PM Motors)
−
2302
2303
2305
2306
2308
230A
230B
230D
Voltage Class
V
200
200
200
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Rated Speed
min
-1
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
Motor Rated Power (for PM Motors)
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0
E5-03
Motor Rated Current (for PM Motors)
A
1.77
3.33
5.94
9.48
14.17
20.42
27.92
39.6
E5-04
Number of Motor Poles (for PM Motors)
–
6
6
6
6
6
6
6
6
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω
3.154 1.835 0.681 0.308 0.405 0.278 0.180 0.098
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH
28.46 19.46 10.00 6.88 8.15 5.77 6.32 3.34
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH
39.29 25.89 15.20 9.25 10.76 8.60 8.80 4.61
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs/rad
268.8 256.9 271.9 260.2 286.8 314.9 300.8 292.3
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/(min
-1
)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum
Voltage
V
190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.0016 0.0022 0.0081 0.0133 0.0133 0.017 0.027 0.044
n5-02
Motor
Acceleration
Time
s
0.092 0.068 0.125 0.139 0.083 0.070 0.082 0.092
n8-49
d-Axis Current for High Efficiency
Control (for PM Motors) (OLV/PM)
%
-7.5
-9.4
-13.9
-10.0
-15.0
-17.9
-22.7
-20.5
No.
Name
Unit
Default Settings
E5-01
Motor Code Selection (for PM Motors)
−
230E
230F
2310
2312
2313
2314
2315
2316
Voltage Class
V
200
200
200
200
200
200
200
200
Rated Power
kW
15
18
22
30
37
45
55
75
Rated Speed
min
-1
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
Motor Rated Power (for PM Motors)
kW
15.0
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
Motor Rated Current (for PM Motors)
A
54.2
68.3
75.2
102.0
131.3
160.4
191.7
257.3
E5-04
Number of Motor Poles (for PM Motors)
–
6
6
6
6
6
6
6
6
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω
0.073 0.055
0.048
0.034 0.023 0.016
0.012
0.007
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH
2.94 2.23 2.08 1.67 1.39 0.94 0.82 0.56
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH
3.65 2.85 2.66 2.04 1.73 1.22 1.06 0.76
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs/rad
305.1 297.6 355.8 355.4 324.0 302.4 337.2
323.4
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/(min
-1
)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum
Voltage
V
190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.054 0.063 0.113 0.137 0.252 0.304 0.41 0.55
n5-02
Motor
Acceleration
Time
s
0.083 0.079 0.118 0.105 0.157 0.156 0.172 0.169
n8-49
d-Axis Current for High Efficiency
Control (for PM Motors) (OLV/PM)
%
-14.6
-16.4
-11.8
-10.5
-14.5
-17.4
-13.9
-17.5
SIEP_C710636_02B_1_0.book 553 ページ 2015年11月25日 水曜日 午後4時56分