![YASKAWA U1000 Series Скачать руководство пользователя страница 376](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114376.webp)
376
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
6.7 Auto-Tuning Fault Detection
6.7 Auto-Tuning Fault Detection
Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop.
Auto-tuning faults do not trigger a multi-function digital output set for fault or alarm output.
An (End
) error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in
the calculations. Check the cause of the (End
) error using the tables in this section and perform Auto-Tuning again
after fixing the cause.
The drive may be used in the application if no cause can be identified despite the existence of an (End
) error.
An (Er-
) error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the
tables in this section, and perform Auto-Tuning again after fixing the cause.
◆
Auto-Tuning Codes, Causes, and Possible Solutions
Table 6.18 Auto-Tuning Codes, Causes, and Possible Solutions
Digital Operator Display
Error Name
End1
Excessive V/f Setting (detected only during Rotational Auto-Tuning, and displayed after Auto-Tuning is complete)
Cause
Possible Solutions
The torque reference exceeded 20% during
Auto-Tuning.
• Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05.
• Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning.
• If possible, disconnect the motor from the load and perform Auto-Tuning. If the load cannot be uncoupled, simply use the
Auto-Tuning results as they are.
The results from Auto-Tuning the no-load current
exceeded 80%.
Digital Operator Display
Error Name
End2
Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete)
Cause
Possible Solutions
Motor data entered during Auto-Tuning was
incorrect.
• Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
• Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the parameter
setting range, assigning the iron-core saturation
coefficient (E2-07, E2-08) a temporary value.
• Check and correct faulty motor wiring.
• Disconnect the motor from machine and perform Rotational Auto-Tuning.
Digital Operator Display
Error Name
End3
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
Cause
Possible Solutions
The correct current rating printed on the nameplate
was not entered into T1-04.
• Check the setting of parameter T1-04.
• Check the motor data and repeat Auto-Tuning.
Digital Operator Display
Error Name
End4
Adjusted Slip Calculation Error
Cause
Possible Solutions
The slip that was calculated is outside the allowable
range.
• Make sure the data entered for Auto-Tuning is correct.
• Execute Rotational Auto-Tuning instead. If not possible, try Stationary Auto-Tuning 2.
Digital Operator Display
Error Name
End5
Resistance Tuning Error
Cause
Possible Solutions
The resistance value that was calculated is outside
the allowable range.
• Double check the data that was entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.
Digital Operator Display
Error Name
End6
Leakage Inductance Alarm
Cause
Possible Solutions
A1-02 setting error
• Check the setting of parameter A1-02.
• Check the control mode and repeat Auto-Tuning.
The leakage inductance value that was calculated is
outside the allowable range.
Double check the data that was entered for the Auto-Tuning process.
Digital Operator Display
Error Name
End7
No-Load Current Alarm
Cause
Possible Solutions
The entered no-load current value was outside the
allowable range.
Check and correct faulty motor wiring.
Auto-Tuning results were less than 5% of the motor
rated current.
Double check the data that was entered for the Auto-Tuning process.
Digital Operator Display
Error Name
Er-01
Motor Data Error
Cause
Possible Solutions
Motor data or data entered during Auto-Tuning was
incorrect.
• Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-Tuning.
• Start Auto-Tuning over again and enter the correct information.
SIEP_C710636_02B_1_0.book 376 ページ 2015年11月25日 水曜日 午後4時56分