![YASKAWA U1000 Series Скачать руководство пользователя страница 434](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114434.webp)
8.2 Drive Options and Peripheral Devices
434
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Others
–
DriveWizard Plus
–
PC tool for drive setup and parameter management
–
DriveWorksEZ
–
PC tool for enhanced programming of the drive
Communication Options
Motor PG Feedback Open Collector
Interface
PG-B3
For speed feedback input by connecting a motor encoder
Input: 3 track (can be used with one or two tracks), for HTL
encoder connection, 50 kHz max
Output: 3 track, open collector
Encoder power supply: 12 V, max current 200 mA
Motor PG Feedback Line Driver
Interface
PG-X3
For speed feedback input by connecting a motor encoder
Input: 3 track (can be used with one or two tracks), line driver,
300 kHz max
Pulse monitor: Matches RS-422 level
Encoder power supply: 5 V or 12 V, max current 200 mA
EnDat Encoder
PG-F3
For speed feedback input by connecting a motor encoder
Encoder type: EnDat 2.1/01, EnDat 2.2/01, and EnDat 2.2/
22(HEIDENHAIN), HIPERFACE (SICK STEGMANN)
Maximum input frequency: 20 kHz
Pulse monitor: Matches RS-422 level
Output voltage: 5 V
±
5%, 8 V
±
10%
Maximum output current: 200 mA
Encoder power supply: 5 V, max current 330 mA or 8 V, max
current 150 mA
Wiring length: 20 m max. for the encoder, 30 m max. for the
pulse monitor
Note:
This option card can only be used in CLV/PM.
Motor Feedback Resolver Interface
PG-RT3
For motor speed feedback by connecting a resolver
(TS2640N321E64 by Tamagawa Seiki Co., LTD).
Input voltage: 10 Vac rms 10 kHz
Transformation ratio: 0.5
±
5%
maximum input current: 100 mA rms
Analog Input
AI-A3
Allows high precision, high resolution analog reference input
Input channels: 3
Voltage input: -10 to 10 Vdc (20 k
Ω
), 13 bit signed
Current input: 4 to 20 mA or 0 to 20 mA (250
Ω
), 12 bit
Analog Monitor
AO-A3
Provides extra multi-function analog output terminals.
Output channels: 2
Output voltage: -10 to 10 V, 11 bit (signed)
Digital Input
DI-A3
Used to set the frequency reference by digital inputs
Input channels: 18 (including SET signal and SIGN signal)
Input signal type: BCD 16 bit (4 digit), 12 bit (3 digit), 8 bit (2
digit)
Input signal: 24 Vdc, 8 mA
Digital Output
DO-A3
Provides extra insulated multi-function digital outputs.
Photocoupler relays: 6 (48 V, up to 50 mA)
Contact relays: 2 (250 Vac/up to 1 A, 30 Vdc/up to 1 A)
PROFIBUS-DP
SI-P3
Connects to a PROFIBUS-DP network.
CC-Link
SI-C3
Connects to a CC-Link network
DeviceNet
SI-N3
Connects to a DeviceNet network
Option
Model Number
Description
SIEP_C710636_02B_1_0.book 434 ページ 2015年11月25日 水曜日 午後4時56分