4.6 Application Selection
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
149
St
ar
t-
Up Pr
ogr
ammi
ng
&
O
p
er
at
io
n
4
◆
Setting 2: Conveyor Application
Table 4.8 Conveyor: Parameter Settings
Table 4.9 Conveyor: User Parameters (A2-01 to A2-16)
◆
Setting 3: Exhaust Fan Application
Table 4.10 Exhaust Fan: Parameter Settings
Table 4.11 Exhaust Fan: User Parameters (A2-01 to A2-16)
◆
Setting 4: HVAC Fan Application
Table 4.12 HVAC Fan: Parameter Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Drive Duty Mode Selection
0: Heavy Duty (HD)
No.
Parameter Name
No.
Parameter Name
A1-02
Control Method Selection
C1-01
Acceleration Time 1
b1-01
Frequency Reference Selection 1
C1-02
Deceleration Time 1
b1-02
Run Command Selection 1
E2-01
Motor Rated Current
No.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C6-01
Drive Duty Mode Selection
1: Normal Duty (ND)
E1-03
V/f Pattern Selection
F: Custom V/f pattern
E1-07
Middle Output Frequency
30.0 Hz
E1-08
Middle Output Frequency Voltage
50.0 V
L2-01
Momentary Power Loss Operation Selection
1: Enabled
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-07
Middle Output Frequency
b1-02
Run Command Selection 1
E1-08
Middle Output Frequency Voltage
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
b3-01
Speed Search Selection at Start
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
C1-01
Acceleration Time 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
C1-02
Deceleration Time 1
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
E1-03
V/f Pattern Selection
L5-01
Number of Auto Restart Attempts
No.
<1> Max. setting value varies by the drive model selection (o2-04).
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
b1-17
Run Command at Power Up
1: Run command issued, motor operation start
C6-01
Drive Duty Model Selection
1: Normal Duty (ND)
C6-02
Carrier Frequency Selection
1: 4.0 Hz
H2-03
CIMR-UA
, CIMR-UD
, CIMR-UT
:Terminal P1-PC Function
Selection (Open-collector)
CIMR-UB
:Terminal M3-M4 Function Selection (Relay)
39: Watt Hour Pulse Output
L2-01
Momentary Power Loss Operation Selection
2: CPU Power Active - Drive will restart if power returns prior to control power supply shut
down.
L8-03
Overheat Pre-Alarm Operation Selection
4: Operation at lower speed
L8-38
Carrier Frequency Reduction Selection
2: Enabled across entire frequency range.