![YASKAWA U1000 Series Скачать руководство пользователя страница 541](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114541.webp)
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
541
t
B
No.
Name
Unit
Default Settings
Model CIMR-U
–
4
0077
4
0096
4
0124
4
0156
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model Selection
Hex.
A1
A2
A3
A4
E2-11 (E4-11)
Motor rated Output
kW
30
37
37
45
45
55
55
75
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
80
80
60
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.8
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
0.50
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
92.54
76.32
76.32
71.56
71.56
67.2
67.2
46.2
C5-17 (C5-37)
Motor Inertia
kgm
2
0.220
0.273
0.273
0.333
0.333
0.490
0.490
0.900
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01)
Motor Rated Current
A
52.3
65.6
65.6
79.7
79.7
95
95
130
E2-02 (E4-02)
Motor Rated Slip
Hz
1.8
1.33
1.33
1.6
1.6
1.46
1.46
1.39
E2-03 (E4-03)
Motor No-Load Current
A
10.9
19.1
19.1
22
22
24
24
36
E2-05 (E4-05)
Motor Line to Line Resistance
Ω
0.269
0.155
0.155
0.122
0.122
0.088
0.088
0.092
E2-06 (E4-06)
Motor Leakage Inductance
%
20.7
18.8
18.8
19.9
19.9
20
20
20
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
750
925
925
1125
1125
1260
1260
1600
E5-01
Motor Code Selection (for PM Motors)
Hex.
1242
1242
1243
1243
1244
1244
1245
1245
L2-02
Momentary Power Loss Ride-Thru Time
s
1.1
1.1
1.1
1.2
1.2
1.2
1.2
1.3
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.6
0.6
0.6
0.6
0.6
1
1
1
L2-04
Momentary Power Loss Voltage Recovery Time
V
300
300
300
300
300
300
300
300
L8-02
Overheat Alarm Level
°
C
130
130
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
30
30
n5-02
Motor Acceleration Time
s
0.323
0.32
0.32
0.387
0.387
0.317
0.317
0.533
No.
Name
Unit
Default Settings
Model CIMR-U
–
4
0180
4
0216
4
0240
4
0302
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive Model Selection
Hex.
A5
A6
A7
A8
E2-11 (E4-11)
Motor rated Output
kW
75
90
90
110
110
132
132
160
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
b8-03
Energy Saving Control Filter Time Constant
s
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
46.2
38.91
38.91
36.23
36.23
32.79
32.79
30.13
C5-17 (C5-37)
Motor Inertia
kgm
2
0.900
1.100
1.10
1.90
1.90
2.10
2.10
3.30
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01)
Motor Rated Current
A
130
156
156
190
190
223
223
270
E2-02 (E4-02)
Motor Rated Slip
Hz
1.39
1.4
1.4
1.4
1.4
1.38
1.38
1.35
E2-03 (E4-03)
Motor No-Load Current
A
36
40
40
49
49
58
58
70
E2-05 (E4-05)
Motor Line to Line Resistance
Ω
0.092
0.056
0.056
0.046
0.046
0.035
0.035
0.029
E2-06 (E4-06)
Motor Leakage Inductance
%
20
20
20
20
20
20
20
20
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
1600
1760
1760
2150
2150
2350
2350
2850
E5-01
Motor Code Selection (for PM Motors)
Hex.
1246
1246
1247
1247
1248
1248
1249
1249
L2-02
Momentary Power Loss Ride-Thru Time
s
1.3
1.5
1.5
1.7
1.7
1.7
1.7
1.8
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1
1
1
1
1
1
1
L2-04
Momentary Power Loss Voltage Recovery Time
V
300
300
300
300
300
300
300
300
L8-02
Overheat Alarm Level
°
C
130
130
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
30
30
30
30
30
30
30
30
n5-02
Motor Acceleration Time
s
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
SIEP_C710636_02B_1_0.book 541 ページ 2015年11月25日 水曜日 午後4時56分