5.5 E: Motor Parameters
5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
◆
E1: V/f Pattern for Motor 1
■
V/f Pattern Settings (E1-03)
The drive uses the V/f pattern that has been set to adjust the output voltage relative to the frequency reference. There are
15 different preset V/f patterns (setting 0 to E) to select from, each with varying voltage profiles, saturation levels
(frequency at which maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is
available (setting F). The custom V/f pattern requires the user to create the pattern using parameters E1-04 through
E1-10.
■
E1-03: V/f Pattern Selection
The user can select the V/f pattern for the drive and motor from 15 predefined patterns, or create a custom V/f pattern.
Setting a Predefined V/f Pattern (Setting 0 to E)
Choose the V/f pattern that best meets the application demands from
. These settings are available only in V/f
Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note: 1.
Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2.
Parameter E1-03 is not reset when the drive is initialized.
Table 5.21 Predefined V/f Patterns
No.
Parameter Name
Setting Range
Default
E1-03
V/f Pattern Selection
0 to F
<1> Parameter setting value is not reset to the default value during drive initialization (A1-03).
F
<2> Settings 0 through E are not available when using any of the vector control modes.
Setting
Specification
Characteristic
Application
0
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters
E1-04 to E1-13 are the same as those of setting 1.
50 Hz
Constant torque
For general purpose applications. Torque remains constant regardless of
changes to speed.
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Heavy Duty 2
Derated torque
For fans, pumps, and other applications where the required torque
changes as a function of the speed.
5
50 Hz, Heavy Duty 1
6
60 Hz, Heavy Duty 1
7
60 Hz, Heavy Duty 2
8
60 Hz, mid starting torque
High starting torque
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m
• A large amount of starting torque is required
9
60 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than 60 Hz.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
60 Hz
Constant torque
For general purpose applications. Torque remains constant regardless of
changes to speed.