5.3 C: Tuning
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
227
5
■
C5-28: Motor 2 ASR Integral Limit
Functions for motor 2 in the same way that C5-08 functions for motor 1.
Sets the upper limit for ASR as a percentage of the rated load.
■
C5-32: Integral Operation during Accel/Decel for Motor 2
Functions for motor 2 in the same way that C5-12 functions for motor 1.
Enables integral operation during acceleration and deceleration. Refer to
C5-12: Integral Operation during Accel/Decel
for more details.
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
■
C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio
These parameters function for motor 2 in the same way that C5-17 and C5-18 function for motor 1.
These parameters are set automatically when Inertia Tuning and ASR Tuning are performed for motor 2 in CLV and
CLV/PM control modes.
Refer to Auto-Tuning on page 154
for details on Auto-Tuning or enter the data manually.
◆
C6: Carrier Frequency
■
C6-01: Drive Duty Mode Selection
The drive has two different “duty modes” to select from based on the load characteristics. The drive rated current,
overload capacity, and maximum output frequency will change depending upon the duty mode selection. Use parameter
C6-01 to select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND. Refer to
Duty and Normal Duty Ratings on page 454
for details about the rated current.
No.
Parameter Name
Setting Range
Default
C5-28
Motor 2 ASR Integral Limit
0 to 400%
400%
No.
Parameter Name
Setting Range
Default
C5-32
Integral Operation during Accel/Decel for Motor 2
0, 1
0
No.
Parameter Name
Setting Range
Default
C5-37
Motor 2 Inertia
0.0001 to 600.00 kgm
2
Determined by C6-01 and o2-04
C5-38
Motor 2 Load Inertia Ratio
0.0 to 6000.0
1.0
No.
Parameter Name
Setting Range
Default
C6-01
Drive Duty Mode Selection
0 or 1
0 (HD)