F7: Communication Option Card (SI-EM3 and SI-EN3)
F7-01 through F7-42 are common settings used for Modbus TCP/IP, and Ethernet/IP option cards. Other parameters in
the F7 group are used for communication protocol specific settings.
For more details on a specific option card, refer to the instruction manual for the option card.
No.(Addr.)
Name
Description
Setting
Page
F7-01
(3E5H)
IP Address 1
Sets the static/fixed IP address.
Parameter F7-01 sets the most significant octet.
Default: 192
Min: 0
Max: 255
–
F7-02
(3E6H)
IP Address 2
Sets the static/fixed IP address.
Parameter F7-02 sets the second most significant octet.
Default: 168
Min: 0
Max: 255
–
F7-03
(3E7H)
IP Address 3
Sets the static/fixed IP address.
Parameter F7-03 sets the third most significant octet.
Default: 1
Min: 0
Max: 255
–
F7-04
(3E8H)
IP Address 4
Sets the static/fixed IP address.
Parameter F7-04 sets the fourth most significant octet.
Default: 20
Min: 0
Max: 255
–
F7-05
(3E9H)
Subnet Mask 1
Sets the static/fixed Subnet Mask.
Parameter F7-05 sets the most significant octet.
Default: 255
Min: 0
Max: 255
–
F7-06
(3EAH)
Subnet Mask 2
Sets the static/fixed Subnet Mask.
Parameter F7-06 sets the second most significant octet.
Default: 255
Min: 0
Max: 255
–
F7-07
(3EBH)
Subnet Mask 3
Sets the static/fixed Subnet Mask.
Parameter F7-07 sets the third most significant octet.
Default: 255
Min: 0
Max: 255
–
F7-08
(3ECH)
Subnet Mask 4
Sets the static/fixed Subnet Mask.
Parameter F7-08 sets the fourth most significant octet.
Default: 0
Min: 0
Max: 255
–
F7-09
(3EDH)
Gateway Address 1
Sets the static/fixed Gateway address.
Parameter F7-09 sets the most significant octet.
Default: 192
Min: 0
Max: 255
–
F7-10
(3EEH)
Gateway Address 2
Sets the static/fixed Gateway address.
Parameter F7-10 sets the second most significant octet.
Default: 168
Min: 0
Max: 255
–
F7-11
(3EFH)
Gateway Address 3
Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.
Default: 1
Min: 0
Max: 255
–
F7-12
(3E0H)
Gateway Address 4
Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.
Default: 1
Min: 0
Max: 255
–
F7-13
(3F1H)
Address Mode at Startup
Selects how the option address is set.
0: Static
1: BOOTP
2: DHCP
Default: 2
Min: 0
Max: 2
–
F7-14
(3F2H)
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Min: 0
Max: 2
–
F7-15
(3F3H)
Communication Speed Selection
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
Default: 10
Min: 10
Max: 100
–
F7-16
(3F4H)
Communication Loss Time-out
Sets the time-out value for communication loss detection in tenths of a second. A value of 0
disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min: 0
Max: 300
–
F7-17
(3F5H)
EtherNet/IP Speed Scaling Factor
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
F7-18
(3F6H)
EtherNet/IP Current Scaling Factor
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID 2AH Object.
Default: 0
Min: -15
Max: 15
–
All Modes