4.7 Auto-Tuning
160
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note:
These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning.”
Note: 1.
For details on each setting, refer to
Parameter Settings during Induction Motor Auto-Tuning: T1 on page 161
2.
To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
Step
Display/Result
1.
Press
to access the motor output power parameter T1-02.
The value set for E2-11 prior to turning on the power is displayed for T1-02.
2.
The setting value of T1-02 flashes when
is pressed.
The setting can be changed.
3.
Press
,
,
,
and
to enter the motor power nameplate data in kW.
4.
Press
to save the setting.
5.
The display automatically returns to the display in Step 1.
6.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Frequency
• T1-09, Motor No-Load Current (Stationary Auto-Tuning 2 only)
• T1-10, Motor Rated Slip (Stationary Auto-Tuning 2 only)
- A.TUNE -
T1-
02
= 0.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
ESC
FWD
DATA
“0.75kW”
- A.TUNE -
T1-02=
0
00.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
FWD
“0.75kW”
F1
F2
- A.TUNE -
T1-02= 000.4
0
kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
FWD
“0.75kW”
Entry Accepted
- A.TUNE -
T1-
02
= 0.40kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
ESC
FWD
DATA
“0.75kW”
- A.TUNE -
T1-
10
= X.XX Hz
(0.00 ~ 20.00)
PRG
Mtr Rated Slip
ESC
FWD
DATA
“X.XX Hz”
- A.TUNE -
T1-
03
= 200.0VAC
(0.0 ~ 255.0)
PRG
Rated Voltage
ESC
FWD
DATA
“200.0VAC”
SIEP_C710636_02B_1_0.book 160 ページ 2015年11月25日 水曜日 午後4時56分