![YASKAWA U1000 Series Скачать руководство пользователя страница 529](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114529.webp)
B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
529
t
B
■
U5: PID Monitors
■
U6: Control Monitors
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
U5-01
(57H)
PID Feedback
Displays the PID feedback value.
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-02
(63H)
PID Input
Displays the amount of PID input (deviation between PID setpoint and feedback).
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-03
(64H)
PID Output
Displays PID control output.
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-04
(65H)
PID Setpoint
Displays the PID setpoint.
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-05
(7D2H)
PID Differential Feedback
Displays the 2nd PID feedback value if differential feedback is used (H3-
= 16).
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-06
(7D3H)
PID Adjusted Feedback
Displays the difference of both feedback values if differential feedback is used (U5-01) -
(U5-05). If differential feedback is not used, then U5-01 and U5-06 will be the same.
10 V: 100%
(-10 to +10 V)
0.01%
–
U5-21
(872H)
Automatically Calculated
Energy Saving Coefficient Ki
Value
Displays the energy saving coefficient Ki value.
No signal output
available
0.01
–
U5-22
(873H)
Automatically Calculated
Energy Saving Coefficient Kt
Value
Displays the energy saving coefficient Kt value.
No signal output
available
0.01
–
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
U6-01
(51H)
Motor Secondary Current (Iq)
Displays the value of the motor secondary current (Iq). Motor rated secondary current is 100%.
10 V: Motor
secondary rated
current
(-10 to +10 V)
0.1%
–
U6-02
(52H)
Motor Excitation Current (Id)
Displays the value calculated for the motor excitation current (Id). Motor rated secondary
current is 100%.
10 V: Motor
secondary rated
current
(-10 to +10 V)
0.1%
–
U6-03
(54H)
ASR Input
Displays the input and output values when using ASR control.
10 V: Max frequency
(-10 to +10 V)
0.01%
–
U6-04
(55H)
ASR Output
10 V: Motor
secondary rated
current
(-10 to +10 V)
U6-05
(59H)
Output Voltage Reference (Vq)
Output voltage reference (Vq) for the q-axis.
10 V: 200 Vrms
(-10 to +10 V)
0.1 Vac
–
U6-06
(5AH)
Output Voltage Reference (Vd)
Output voltage reference (Vd) for the d-axis.
10 V: 200 Vrms
(-10 to +10 V)
0.1 Vac
–
U6-07
(5FH)
q-Axis ACR Output
Displays the output value for current control relative to motor secondary current (q-axis).
10 V: 200 Vrms
(-10 to +10 V)
0.1%
–
U6-08
(60H)
d-Axis ACR Output
Displays the output value for current control relative to motor secondary current (d-axis).
10 V: 200 Vrms
(-10 to +10 V)
0.1%
–
U6-09
(7C0H)
Advance Phase Compensation
(
Δθ
)
Displays the degree of forward phase correction after calculating the deviation of
Δθ
cmp.
10 V: 180 deg
-10 V: -180 deg
(-10 to +10 V)
0.1 deg
–
U6-10
(7C1H)
Control Axis Deviation (
Δθ
)
Displays the amount of deviation between the actual d-axis / q-axis and the
γ
-axis /
δ
-axis used
for motor control.
10 V: 180 deg
-10 V: -180 deg
(-10 to +10 V)
0.1 deg
–
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
SIEP_C710636_02B_1_0.book 529 ページ 2015年11月25日 水曜日 午後4時56分