![YASKAWA U1000 Series Скачать руководство пользователя страница 290](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114290.webp)
5.7 H: Terminal Functions
290
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Figure 5.81
Figure 5.81 Accel/Decel Time Gain with Analog Input Terminal
Setting 6: DC Injection Braking current
The current level used for DC Injection Braking. Set as a percentage of the maximum output current using.
Figure 5.82
Figure 5.82 DC Injection Braking Current Using an Analog Input Terminal
Setting 7: Overtorque/Undertorque Detection level
Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog
input. The analog input will replace the level set to L6-02. An analog input of 100% (10 V or 20 mA) will set a torque
detection level equal to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection
level settings are required.
Refer to L6: Torque Detection on page 310
for details on torque detection.
Setting 8: Stall Prevention level
This setting allows an analog input signal to adjust the Stall Prevention level.
characteristics. The drive will use either the Stall Prevention level set to L3-06 or the level coming from the analog input
terminal that has been selected, whichever value is lower.
Figure 5.83
Figure 5.83 Stall Prevention During Run Using an Analog Input Terminal
Setting 9: Output frequency lower limit level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID feedback
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input Methods on page 203
Setting C: PID setpoint
An input set for this function supplies the PID setpoint value, and the frequency reference selected in parameter b1-01 is
no longer the PID setpoint. PID operation to be enabled in b5-01 to use this setting.
Setting D: Frequency bias
The input value of an analog input set to this function will be added to the frequency reference. This function can be used
with any frequency reference source.
100%
50%
0
5 V
10 V
1V 2V
20%
10%
Acceleration/deceleration gain from 1 to 10 V
(10 V)
Input Voltage (V)
×
10 (%)
=
Drive Rated
Current
0
(4)
100%
10 V
(20 mA)
DC Injection Braking Current Level
Stall Prevention Level during Run
30%
100%
Analog Input Level
30%
100%
0
SIEP_C710636_02B_1_0.book 290 ページ 2015年11月25日 水曜日 午後4時56分