5.5 E: Motor Parameters
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
255
5
Note: 1.
E5-
parameters are not reset when the drive is initialized using parameter A1-03.
2.
When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03.
3.
Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.
4.
Set E5-01 to FFFF when using a motor other than a Yaskawa SMRA, SSR1, or SST4 series.
5.
Default settings are:
• OLV/PM, AOLV/PM: Yaskawa SSR1 Series (1750 min
-1
)
• CLV/PM: Yaskawa SST4 Series (1750 min
-1
)
6.
Selection may vary depending on the motor code entered to E5-01.
7.
If an alarm or hunting occurs even though a motor code is used, enter the value indicated on the name plate. For details, refer to
Auto-Tuning for Permanent Magnet Motors on page 155
explains the motor code setting.
Figure 5.55
Figure 5.55 PM Motor Code
■
E5-02: Motor Rated Power (for PM Motors)
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors or
by entering the motor code to E5-01.
■
E5-03: Motor Rated Current (for PM Motors)
Sets the motor rated current in amps. This parameter is automatically set when the value is entered to T2-06 during the
Auto-Tuning process.
Note:
Display is in the following units.
CIMR-U
2
0028, 2
0042, and 4
0011 to 4
0027: 0.01 A units
CIMR-U
2
0054 to 2
0248, and 4
0034 to 4
0930: 0.1 A units
■
E5-04: Number of Motor Poles (for PM Motors)
Sets the number of motor poles. This parameter is automatically set when the value is entered to T2-08 during the
Auto-Tuning process.
■
E5-05: Motor Stator Resistance (r1) (for PM Motors)
Set the resistance for one motor phase. When measuring the resistance manually, make sure not to enter the line-to-line
resistance into E5-05.
No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power (for PM Motors)
0.10 to 650.00 kW
Determined by E5-01
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current (for PM Motors)
10 to 150% of drive rated current
Determined by E5-01
No.
Parameter Name
Setting Range
Default
E5-04
Number of Motor Poles (for PM Motors)
2 to 48
Determined by E5-01
No.
Parameter Name
Setting Range
Default
E5-05
Motor Stator Resistance (r1) (for PM Motors)
0.000 to 65.000
Ω
Determined by E5-01
0 0 0 0
0: 1800 min
-1
Series
1: 3600 min
-1
Series
2: 1750 min
-1
Series
3: 1450 min
-1
Series
4: 1150 min
-1
Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
2: Rated Torque for IPM
Motors
(SST4 Series)
SIEP_C710636_02B_1_0.book 255 ページ 2015年11月25日 水曜日 午後4時56分